Field Protocols

BACnet

BACnet support is built on the rustbac family of crates (rustbac-core, rustbac-client, rustbac-datalink, rustbac-bacnet-sc, rustbac-mstp) and covers the full range of BACnet services needed for a production building automation system.

Transport modes

OpenCrate supports five BACnet transport modes, all managed through a unified TransportClient enum that wraps Arc<BacnetClient<T>>. The with_client! macro dispatches calls to the correct transport without generic proliferation in calling code.

Mode Config key Description
IP mode: "ip" Standard BACnet/IP unicast and broadcast on UDP port 47808. The default for most installations.
IPv6 mode: "ipv6" BACnet/IP over IPv6 networks.
Foreign (BBMD) mode: "foreign" Registers with a BACnet Broadcast Management Device for cross-subnet communication. Requires bbmd_addr and ttl in config. Uses BacnetClient::new_foreign().
BACnet/SC mode: "secure_connect" BACnet Secure Connect over WebSocket with TLS. Requires hub_endpoint. Uses BacnetClient::new_sc().
MS/TP mode: "mstp" RS-485 serial via the rustbac-mstp crate. Implements the MS/TP data link layer with CRC-8 (header) and CRC-16 (data) validation, frame encode/decode, and preamble scanning. Requires serial_port, baud_rate, mac_address, and max_master.

Multi-network support

BacnetNetworks manages multiple concurrent BacnetBridge instances, each keyed by a network_id string (e.g., "ip-main", "mstp-field"). This allows a single OpenCrate instance to communicate across segmented BACnet networks simultaneously.

Configuration uses ScenarioSettings.bacnet_networks, a map of network IDs to BacnetNetworkConfig objects. Legacy configurations with a single bacnet field are automatically wrapped as {"default": config} through resolved_bacnet_networks().

{
  "bacnet_networks": {
    "ip-main": {
      "mode": "ip",
      "monitor_interval_secs": 300,
      "object_check_cycles": 6,
      "trend_log_sync_interval_secs": 600
    },
    "mstp-field": {
      "mode": "mstp",
      "serial_port": "/dev/ttyUSB0",
      "baud_rate": 76800,
      "mac_address": 1,
      "max_master": 127
    }
  }
}

BacnetNetworkConfig fields:

Field Default Description
mode "ip" Transport mode (ip, ipv6, foreign, secure_connect, mstp)
bbmd_addr -- BBMD address for foreign mode
ttl -- Time-to-live for BBMD registration
hub_endpoint -- WebSocket endpoint for BACnet/SC
server_device_instance -- Device instance for the local BACnet server
serial_port -- Serial port path for MS/TP
baud_rate -- Baud rate for MS/TP
mac_address -- MS/TP MAC address (0-127)
max_master -- Highest MS/TP master address to poll
monitor_interval_secs 300 Interval for background device monitoring
object_check_cycles 6 Monitor cycles between object list change checks
trend_log_sync_interval_secs 600 Interval for trend log backfill sync

Discovery

Discovery is always user-initiated and never runs automatically on startup. Re-discovery preserves existing device state (accepted devices stay accepted).

Scan process:

  1. OpenCrate broadcasts Who-Is on the selected network(s).
  2. Responding devices are recorded as DiscoveredDevice entries with protocol-agnostic fields plus protocol_meta JSON carrying BACnet-specific data.
  3. For each device, OpenCrate reads the full object list and creates DiscoveredPoint entries.
  4. Device metadata is enriched by reading: VendorName, ModelName, FirmwareRevision, Location, Description, MaxApduLengthAccepted, SegmentationSupported, ProtocolVersion, and ApplicationSoftwareVersion.

Parallel multi-network scan: scan_bacnet_all() scans all configured networks concurrently using join_all. Single-network configurations skip the parallelism overhead.

Who-Has discovery: who_has_by_id() and who_has_by_name() provide broadcast discovery of specific objects by identifier or name string.

Accepting devices: When a discovered device is accepted, OpenCrate creates nodes and entities with auto-generated tags in a single pass. Each discovered point includes network_id in its protocol_meta, enabling write routing to the correct network.

Device monitoring

A background monitor loop runs continuously after startup:

  • Who-Is polling: Sends Who-Is to all known devices at a configurable interval (default 300 seconds).
  • Offline detection: A device that misses two consecutive poll cycles triggers a DeviceDown event.
  • Recovery detection: When an offline device responds again, it is automatically recovered.
  • Passive discovery: New devices that respond to Who-Is broadcasts but were not previously known are recorded.
  • Object list change detection: Every N monitor cycles (default 6, approximately every 30 minutes), the monitor reads the ObjectList length for each device. A mismatch publishes an ObjectListChanged event, and the discovery store marks the device as object_list_stale.

The monitor publishes a DeviceMonitorCycle summary event after each complete cycle.

Reading values

Poll loop: Reads PresentValue and StatusFlags together for each monitored point. StatusFlags (IN_ALARM, FAULT, OVERRIDDEN, OUT_OF_SERVICE) are mapped to internal PointStatusFlags.

Change of Value (COV): Supports both SubscribeCOV and SubscribeCOVProperty for granular property-level subscriptions. COV notifications are processed through the same StatusFlags mapping. Subscriptions can be cancelled with cancel_cov_property_subscription().

Priority array: read_priority_array(device_instance, object_id) reads all 16 priority levels plus the RelinquishDefault, returning a PriorityArrayInfo structure. The GUI provides a dropdown for selecting write priority (1-16) with standard BACnet priority labels.

Writing values

Network-aware routing: The write handler extracts the BACnet device instance via extract_bacnet_instance(), then calls find_network_for_device() to route the write to the correct BacnetBridge. If direct routing fails, it iterates all networks as a fallback.

Write priority: PointSource::write_point accepts an optional priority: Option<u8> parameter (1-16). The GUI exposes this as a priority dropdown with BACnet-standard labels.

Trend logs

read_trend_log reads trend log entries from a device. backfill_trend_log replays historical data from a device's trend log buffer into the local history store.

The sync interval is configurable per network (default 600 seconds). reset_trend_log_backfill() restarts the sync loop with fresh state. The discovery UI provides a per-entry Backfill button for manual triggering.

Schedule interop

Full read/write support for BACnet schedule objects:

Function Description
read_schedule Read a schedule object's weekly schedule
write_schedule Write a weekly schedule to a device
read_schedule_default Read the schedule's default value
read_calendar Read a calendar object's date list
read_exception_schedule Read exception schedule entries

The schedule view includes a BACnet Sync panel with Read/Write from Device buttons for bidirectional synchronization.

Intrinsic reporting and alarms

Event polling: A background loop checks recv_event_notification and calls GetEventInformation for each device every 60 seconds. Events are enriched with acknowledged_transitions, notify_type, event_enable, and event_priorities.

Alarm acknowledgment: acknowledge_alarm() sends the AcknowledgeAlarm service to the remote device. The GUI Ack button automatically sends a BACnet acknowledgment for devices with bacnet- prefixed IDs.

Alarm/event queries: get_alarm_summary() and get_enrollment_summary() are also exposed for bulk alarm state retrieval.

Device management

Function Description
reinitialize_device Warmstart or coldstart a remote device (split buttons in UI)
device_communication_control Enable or disable communication on a device
sync_time Send UTC time synchronization (also runs automatically every 4 hours)
get_event_info Retrieve event information (shown in Events table in discovery UI)

Object management

Function Description
create_object Create a new BACnet object on a remote device
delete_object Delete a BACnet object from a remote device

The commissioning UI in the discovery view provides a type selector for object creation.

File transfer

Function Description
read_file_stream Stream-read a file from a device
read_file_record Record-read a file from a device
write_file_stream Stream-write a file to a device
write_file_record Record-write a file to a device

A File Transfer UI panel is available in the discovery view for accepted devices.

Private transfer

private_transfer() sends vendor-specific PrivateTransfer requests for integrations that extend beyond the standard BACnet service set.

BACnet server

OpenCrate can act as a BACnet server, exposing local points to other BACnet devices on the network:

  • Service handlers: WritePropertyMultiple, SubscribeCOV, CreateObject, DeleteObject
  • COV subscription manager: Tracks subscriptions with lifetime and expiry. Generates UnconfirmedCOVNotification messages when subscribed properties change.
  • Object store: Populated from the local PointStore via init_server_store().
  • Configuration: server_device_instance in BacnetNetworkConfig sets the device instance number for the local server.

Reconnection

Per-device exponential backoff with a 2-second base and 5-minute maximum. After 5 consecutive failures, a DeviceDown event is published. Devices automatically recover when communication is restored.


Modbus

Modbus support is built on the rustmod family of crates (rustmod-core, rustmod-client, rustmod-datalink) and provides TCP and RTU transport with full function code coverage.

Transport modes

ModbusTransport is an enum wrapping TCP and RTU variants, dispatching all read/write methods uniformly.

Mode Description
TCP One persistent connection per device, stored in clients: HashMap<String, Arc<ModbusTransport>>. Writes reuse existing connections.
RTU Shared serial transport keyed by port via the rustmod-datalink rtu feature. All RTU devices on the same bus share one serial connection. Configured with serial_port, baud_rate.

Configuration through ModbusNetworkConfig:

{
  "modbus": {
    "mode": "tcp",
    "default_timeout_ms": 1000,
    "default_retry_count": 3
  }
}

For RTU:

{
  "modbus": {
    "mode": "rtu",
    "serial_port": "/dev/ttyUSB1",
    "baud_rate": 9600
  }
}

Per-device client configuration

Each device can override defaults through ModbusDefaults:

Field Description
response_timeout_ms Maximum wait time for a device response
retry_count Number of retries before marking a read as failed
throttle_delay_ms Minimum delay between consecutive requests to a device

Block reads

plan_block_reads() coalesces contiguous or nearby register addresses into block reads to minimize network round-trips:

  • Maximum gap: 10 registers. Addresses within this gap are read as a single block even if not all are mapped.
  • Block size cap: 125 registers (holding/input registers) or 2000 bits (coils/discrete inputs), matching Modbus protocol limits.
  • Result: One read per block instead of N individual reads. Points are extracted from the block response by offset.

Bit extraction

Individual bits or bit fields within a register are accessible through ModbusPointMapping fields:

  • bit_offset: Option<u8> -- Extract a single bit at this position.
  • bit_mask: Option<u16> -- Extract a masked bit field from the register.

apply_bit_extraction() handles the extraction. When writing to a point with bit_mask, FC22 (Mask Write Register) is used automatically to modify only the relevant bits without disturbing other bits in the register.

Function code support

FC Function Description
FC1-4 Standard reads Read coils, discrete inputs, holding registers, input registers
FC5-6, FC15-16 Standard writes Write single/multiple coils and registers
FC8 Diagnostics Echo test, bus message counters, clear counters. Exposed through diagnostics(device_id, sub_function, data).
FC22 Mask Write Register Atomic bit-level register modification. Used automatically for points with bit_mask. Exposed through mask_write_register(device_id, addr, and_mask, or_mask).
FC23 Read/Write Multiple Atomic read and write in a single transaction via read_write_multiple().
FC24 Read FIFO Queue Queue read via read_fifo(device_id, addr).
FC43 Read Device Identification Returns DeviceIdInfo { vendor, product, revision }. Used during discovery enrichment.

Register browser

read_registers() and read_bits() support arbitrary register reads from the GUI, independent of configured point mappings. This is useful for commissioning and troubleshooting. The Modbus Registers tab in the discovery view provides the interface.

Discovery

Modbus devices do not self-describe their register maps, so discovery focuses on device presence detection and identity enrichment:

Configured device scan: Reads all devices defined in the scenario configuration and verifies they respond.

TCP unit ID probe: scan_unit_ids(host, port, start, end) probes a range of unit IDs with a test read (1-second timeout, no retries). Each responding unit ID is checked with FC43 for vendor/model/firmware information.

RTU bus scan: scan_rtu_unit_ids(start, end) performs the same probe over the existing RTU serial bus. is_rtu() exposes the bridge mode so the GUI can adapt the scan form (TCP vs RTU).

Discovery UI adaptation: The collapsible scan form adapts based on bridge mode. Protocol badges are color-coded (blue for BACnet, amber for Modbus). The Modbus overview tab explains that Modbus does not self-describe registers and directs users to profiles and the Registers tab.

Profile library

Pre-built device profiles in profiles/modbus-library/ provide register maps for common devices:

  • generic-power-meter -- Generic power meter template
  • schneider-pm5300 -- Schneider Electric PM5300 power meter
  • abb-acs580 -- ABB ACS580 variable frequency drive

load_profile_library(dir) loads all JSON profiles from the directory. match_profile(profile, vendor, model) scores each profile 0.0-1.0 by manufacturer and model string similarity. DiscoveryService::apply_modbus_profile() converts matched profile points into DiscoveredPoint entries with appropriate Modbus bindings.

Custom profiles can be added by placing JSON files in the profile library directory.

Write-back verification

After every write operation, OpenCrate reads the register back to confirm the device accepted the value. If the read-back fails (device busy, timeout), the system falls back to using the written value and logs the discrepancy.

COV filtering

PointStore::set_if_changed() skips event publication and history recording when a polled value is unchanged from the previous read. This reduces event bus noise and history storage for Modbus points that are polled on a fixed interval.

Error handling

ModbusError is a structured enum that preserves the full context of failures:

Variant Description
Exception Device responded with a Modbus exception code (preserved as ExceptionCode)
Transport Network-level failure
Timeout Response not received within deadline
InvalidResponse Response did not match expected format
Encode Request encoding failure

Helper methods is_busy() and is_transport() support retry logic. The poll loop logs the error category for each failure.

Short block response: If a device returns fewer registers than requested, affected points are logged with a warning and marked with FAULT status.

Reconnection

Uses the same DeviceBackoff implementation as BACnet (shared in src/bridge/backoff.rs): exponential backoff with a 2-second base and 5-minute maximum. After 5 consecutive failures, a DeviceDown event is published through the EventBus. Devices recover automatically when communication resumes.

GUI components

Two dedicated tabs appear in the discovery view for accepted Modbus devices:

  • ModbusRegisters (modbus_device_registers.rs): Register browser for arbitrary reads, FC43 device identification display, and FC24 FIFO queue reads.
  • ModbusDiagnostics (modbus_device_diagnostics.rs): FC8 echo test and bus counters, FC22 mask write interface.